12-35
12 Troubleshooting
NJ-series CPU Unit Software User’s Manual (W501)
12-2 Troubleshooting
12
12-2-4 Error Descriptions
Event name Trace Setting Transfer Failure Event code 10260000 hex
Meaning The power supply was interrupted while transferring the trace settings.
Source PLC Function Module Source details None Detection
timing
At power ON or
Controller reset
Error attributes Level Observation Recovery Cycle the power
supply or reset
the Controller.
Log category System
Effects User program Continues. Operation Not affected.
System-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Correction Prevention
The power supply was interrupted
while transferring the trace settings.
Transfer the trace settings again. Do not interrupt the power supply
while transferring the trace settings.
Attached
information
None
Precautions/
Remarks
All trace settings are initialized when this error occurs.
Event name Backup Failed to Start Event code 10290000 hex*
Meaning An error was detected in pre-execution checks for a backup operation.
Source PLC Function Module Source details None Detection
timing
When backup is
specified by the
user
Error attributes Level Observation Recovery --- Log category System
Effects User program Continues. Operation Not affected.
System-defined
variables
Variable Data type Name
None --- ---