Appendices
A-54
NJ-series CPU Unit Software User’s Manual (W501)
*1 This system-defined variable was added for unit version 1.03 of the CPU Unit.
*1 This system-defined variable was added for unit version 1.03 of the CPU Unit.
*1 This system-defined variable was added for unit version 1.03 of the CPU Unit.
*1 This system-defined variable was added for unit version 1.03 of the CPU Unit.
Variable name
_Card1BkupCmd
*1
Member name
.CancelBkup
Meaning Cancel Backup Flag Global/local Global
Function Change this variable to TRUE to cancel backing up data to an SD Memory Card.
Note You cannot use this system-defined variable in the user program. Use it in CIP message communications
when sending a command from an HMI or host computer.
Data type Structure: _sBKUP_CMD, Member: BOOL Range of values TRUE or FALSE
R/W access R/W Retained Not retained. Network Publish Published.
Usage in user program Not possible. Related instruc-
tions
---
Variable name
_Card1BkupCmd
*1
Member name
.ExecVefy
Meaning Execute Verify Flag Global/local Global
Function Change this variable to TRUE to compare the Controller data to a backup file in the SD Memory Card.
Note You cannot use this system-defined variable in the user program. Use it in CIP message communications
when sending a command from an HMI or host computer.
Data type Structure: _sBKUP_CMD, Member: BOOL Range of values TRUE or FALSE
R/W access R/W Retained Not retained. Network Publish Published.
Usage in user program Not possible. Related instruc-
tions
---
Variable name
_Card1BkupCmd
*1
Member name
.CancelVefy
Meaning Cancel Verify Flag Global/local Global
Function Change this variable to TRUE to cancel comparing the Controller data to a backup file in the SD Memory Card.
Note You cannot use this system-defined variable in the user program. Use it in CIP message communications
when sending a command from an HMI or host computer.
Data type Structure: _sBKUP_CMD, Member: BOOL Range of values TRUE or FALSE
R/W access R/W Retained Not retained. Network Publish Published.
Usage in user program Not possible. Related instruc-
tions
---
Variable name
_Card1BkupCmd
*1
Member name
.DirName
Meaning Directory Name Global/local Global
Function Used to specify the directory name in the SD Memory Card for which to back up data.
Note You cannot use this system-defined variable in the user program. Use it in CIP message communications
when sending a command from an HMI or host computer.
Data type Structure: _sBKUP_CMD, Member: STRING(64) Range of values Depends on data type.
R/W access R/W Retained Not retained. Network Publish Published.
Usage in user program Not possible. Related instruc-