3-57
3 System-defined Variables Related to the Built-in EtherNet/IP Port
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
3-3 Specifications for Individual System-defined
Variables
3
Variable name _EIP2_TargetNodeErr [255]
Meaning CIP Communications2 Target Node Error Infor-
mation
Global/local Global
Function Indicates that the connection for the Registered Target Node Information for CIP communications 2 was not estab-
lished or that an error occurred in the target Controller.
The array elements are valid only when the Registered Target Node Information is TRUE.
Array[x]
is TRUE: A connection was not normally established with the target node for a target node ID of x (the Regis-
tered Target Node Information is TRUE and the Normal Target Node Information is FALSE), or a connection was
established with the target node but an error occurred in the target Controller.
Array[x] is FALSE: The target node is not registered for a target node ID of x (the Registered Target Node Informa-
tion is FALSE), or a connection was normally established with the target node (the Registered Target Node Infor-
mation is TRUE and the Normal Target Node Information is TRUE). An error occurred in the target Controller (the
Target PLC Error Information is TRUE).
Note You can use this system-defined variable only for the NX701 CPU Units.
Data type ARRAY [0..255] OF BOOL Range of values TRUE or FALSE
R/W access R Retained Not retained. Network Publish Published.
Usage in user pro-
gram
Possible. Related
instructions
---
Variable name _EIP_NTPResult Member name .ExecTime
Meaning NTP Last Operation Time Global/local Global
Function Gives the last time that NTP processing ended normally.
The time that was obtained from the NTP server is stored when the time is obtained normally.
The time is not stored if it is not obtained from the NTP server normally.
Note Do not use this variable in the user program. There may be a delay in updating it. Use this variable only to
access status through communications from an external device.
Data type Structure: _sNTP_RESULT
Members: DATE_AND_TIME
Range of values Depends on data type.
R/W access R Retained Not retained. Network Publish Published.
Usage in user pro-
gram
Not possible. Related
instructions
You can read the contents of this variable with the GetNTPStatus instruction.
Variable name _EIP_NTPResult Member name .ExecNormal
Meaning NTP Operation Result Global/local Global
Function This variable shows if the NTP operation ended normally.
TRUE: Indicates an NTP normal end.
FALSE: Indicates that NTP operation ended in an error or has not been executed even once.
Note Do not use this variable in the user program. There may be a delay in updating it. Use this variable only to
access status through communications from an external device.
Data type BOOL Range of values TRUE or FALSE
R/W access R Retained Not retained. Network Publish Published.
Usage in user pro-
gram
Not possible. Related
instructions
You can read the contents of this variable with the GetNTPStatus instruction.

Table of Contents

Other manuals for Omron Sysmac NJ-series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Sysmac NJ-series and is the answer not in the manual?

Omron Sysmac NJ-series Specifications

General IconGeneral
BrandOmron
ModelSysmac NJ-series
CategoryComputer Hardware
LanguageEnglish

Related product manuals