8-27
8 CIP Message Communications
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
8-2 CIP Messaging Communications Client Function
8
8-2-8 Sample Programming for CIP Connection (Class 3)
Message Communications
This sample uses CIP class 3 messages to write a variable, read a variable, and send a message. The
Controllers are connected to an EtherNet/IP network. The IP address of the remote node is
192.168.250.2. The following procedure is used.
1
The CIPOpen is used to open a class 3 connection (Large_Forward_Open). The timeout time is
2 s.
2
The CIPWrite instruction is used to write the value of a variable at a remote node. The variable
name at the remote node is WritingDat and the contents of the WriteDat is written to it. Writing-
Dat must be defined as a global variable at the remote node and the Network Publish attribute
must be set.
3
The CIPRead instruction is used to read the value of a variable at a remote node. The value of
the variable OriginalDat at the other node is read and the read value is stored in the ReadDat
variable. OriginalDat must be defined as a global variable at the remote node and the Network
Publish attribute must be set.
4
The CIPSend instruction is used to send an explicit message to a remote node. The contents of
the message is to read identity information (product name). The class ID, instance ID, attribute
ID, and service code are as follows: The response data is stored in the RespDat variable.
5
The CIPClose instruction is used to close the class 3 connection.
8-2-8 Sample Programming for CIP Connection (Class 3) Message
Communications
Item Value
Class ID 1
Instance ID 1
Attribute ID 7
Service code 16#0E
Built-in EtherNet/IP Port Built-in EtherNet/IP Port
IP address: 192.168.250.2
Message sent to read identity
information (product name).
Response
RespDat
Value of variable read.
ReadDat
Variable name: OriginalDat
Global variable
Network Publish attribute
Value of variable written.
WriteDat
Variable name: WritingDat
Global variable
Network Publish attribute

Table of Contents

Other manuals for Omron Sysmac NJ-series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Sysmac NJ-series and is the answer not in the manual?

Omron Sysmac NJ-series Specifications

General IconGeneral
BrandOmron
ModelSysmac NJ-series
CategoryComputer Hardware
LanguageEnglish

Related product manuals