5-9
5
User-set Parameters: A2
A1-04
Password
Password input when a pass-
word has been set in A1-05.
This function write-protects
some parameters of the initial-
ize mode.
If the password is changed,
A1-01 to A1-03 and A2-01 to
A2-32 parameters can no
longer be changed. (Program-
ming mode parameters can be
changed.)
0 to
9999
0 No A A A A 104H 6-144
Enter Pass-
word
A1-05
Password
setting
Used to set a four digit num-
ber as the password.
Usually this parameter is not
displayed. When the Password
(A1-04) is displayed, hold
down the RESET key and
press the Menu key. The pass-
word will be displayed.
0 to
9999
0 No A A A A 105H 6-144
Select Pass-
word
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
Display
A2-01
to
A2-32
User speci-
fied parame-
ters
Used to select the function for
each of the user specified
parameters. User parameters
are the only accessible parame-
ters if Parameter Access Level
is set to user parameters
(A1-01=1)
b1-01
to
S2-05
–NoAAAA
106H to
125H
6-145
User Param
1 to 32
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector