5-57
5
Fault Restart: L5
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
Display
L5-01
Number of
auto restart
attempts
Sets the number of auto restart
attempts.
Automatically restarts after a
fault and conducts a speed
search from the run frequency.
0 to 10 0 No A A A A 49EH 6-61
Num of
Restarts
L5-02
Auto restart
operation
selection
Sets whether a fault digital
output is activated during fault
restart.
0: No output (Fault output is
not activated.)
1: Output (Fault output is
activated.)
0 or 1 0 No A A A A 49FH 6-61
Restart Sel