5-62
5
n1-02
Hunting-pre-
vention gain
Sets the hunting-prevention
gain.
Normally, there is no need to
change this setting.
If necessary, make the adjust-
ments as follows:
• If vibration occurs with
light load, increase the set-
ting.
• If the motor stalls, reduce
the setting.
If the setting is too large, the
voltage will be too suppressed
and the motor may stall.
0.00 to
2.50
1.00 No A A No No 581H
4-14
6-44
Hunt Prev
Gain
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
Display