5-65
5
Digital Operator Functions: o2
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
Display
o2-01
LOCAL/
REMOTE
key enable/
disable
Enables/Disables the Digital
Operator Local/Remote key
0: Disabled
1: Enabled (Switches
between the Digital
Operator and the parame-
ter settings b1-01, b1-02.)
0 or 1 1 No A A A A 505H 6-139
Local/
Remote Key
o2-02
STOP key
during con-
trol circuit
terminal
operation
Enables/Disables the Stop key
in the run mode.
0: Disabled (When the run
command is issued from
an external terminal, the
Stop key is disabled.)
1: Enabled (Effective even
during run.)
0 or 1 1 No A A A A 506H 6-139
Oper Stop
Key
o2-03
User param-
eter initial
value
Clears or stores user initial
values.
0: Stores/not set
1: Begins storing (Records
the set parameters as user
initial values.)
2: All clear (Clears all
recorded user initial
values)
When the set parameters are
recorded as user initial val-
ues, 1110 will be set in A1-03.
0 to 2 0 No A A A A 507H 6-139
User
Defaults
o2-04
kVA selec-
tion
Do not set unless after replac-
ing the control board. (Refer
to page 5-79 for the setting
values).
0 to FF 0 No A A A A 508H 6-139
Inverter
Model #
o2-05
Frequency
reference
setting
method
selection
When the frequency reference
is set on the Digital Operator
frequency reference monitor,
sets whether the Enter key is
necessary or not.
0: Enter key needed
1: Enter key not needed
When set to 1, the Inverter
accepts the frequency refer-
ence without Enter key opera-
tion.
0 or 1 0 No A A A A 509H 6-139
Operator
M.O.P.
o2-06
Operation
selection
when digital
operator is
disconnected
Sets the operation when the
Digital Operator is discon-
nected.
0: Operation continues even
if the Digital Operator is
disconnected.
1: OPR is detected at Digital
Operator disconnection.
Inverter output is switched
off, and the fault output is
operated.
0 or 1 0 No A A A A 50AH 6-139
Oper
Detection
o2-07
Cumulative
operation
time setting
Sets the cumulative operation
time in hour units.
0 to
65535
0 hr No A A A A 50BH 6-140
Elapsed
Time Set