5-80
5
400 V Class Inverters
Param-
eter
Number
Name Unit Factory Setting
- Inverter Capacity kW 0.4 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11
o2-04 kVA selection - 20 21 22 23 24 25 26 27 28
b8-03
Energy-saving filter time con-
stant
sec 0.50 (Open Loop vector)
b8-04 Energy-saving coefficient -
576.40 447.40 338.80 313.60 245.80 236.44 189.50 145.38 140.88
C6-02
Carrier fre-
quency
selection
Normal Duty 1 -
666666666
Normal Duty 2 -
666666663
E2-01
(E4-01)
Motor rated current A 1.00 1.60 3.10 4.20 7.00 7.00 9.80 13.30 19.9
E2-02
(E4-02)
Motor rated slip Hz 2.90 2.60 2.50 3.00 2.70 2.70 1.50 1.30 1.70
E2-03
(E4-03)
Motor no-load current A 0.60 0.80 1.40 1.50 2.30 2.30 2.60 4.00 5.6
E2-05
(E4-05)
Motor line-to-line resistance W
38.198 22.459 10.100 6.495 3.333 3.333 1.595 1.152 0.922
E2-06
(E4-06)
Motor leak inductance % 18.2 14.3 18.3 18.7 19.3 19.3 18.2 15.5 19.6
E2-10
Motor iron loss for torque com-
pensation
W 14 26 53 77 130 130 193 263 385
E2-11
(E4-07)
Motor rated output power kW 0.40 0.75 1.50 2.20 3.70 4.00 5.00 7.50 11.00
L2-02
Momentary power loss ride
through time
sec 0.1 0.1 0.2 0.3 0.5 0.5 0.8 0.8 1.0
L2-03 Min. baseblock (BB) time sec 0.1 0.2 0.3 0.4 0.5 0.6 0.6 0.7 0.8
L2-04 Voltage recovery time sec 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
L8-02 Overheat pre-alarm level °C959595909595959095
Param-
eter
Number
Name Unit Factory Setting
- Inverter Capacity kW 15 18.5 22 30 37 45 55 75 90
o2-04 kVA selection - 29 2A 2B 2C 2D 2E 2F 30 31
b8-03
Energy-saving filter time con-
stant
sec 0.50 (Open Loop vector)
2.00 (Open Loop
vector)
b8-04 Energy-saving coefficient -
126.26 115.74 103.58 92.54 76.32 71.56 67.20 46.20 38.91
C6-02
Carrier fre-
quency
selection
Normal Duty 1 -
666444433
Normal Duty 2 -
444333223
E2-01
(E4-01)
Motor rated current A 26.5
32.9 38.6 52.3 65.6 79.7 95.0 130.0 156.0
E2-02
(E4-02)
Motor rated slip Hz 1.60 1.67 1.70 1.80 1.33 1.60 1.46 1.39 1.40
E2-03
(E4-03)
Motor no-load current A 7.6 7.8 9.2 10.9 19.1 22.0 24.0 36.0 40.0
E2-05
(E4-05)
Motor line-to-line resistance W
0.550 0.403 0.316 0.269 0.155 0.122 0.088 0.092 0.056
E2-06
(E4-06)
Motor leak inductance % 17.2 20.1 23.5 20.7 18.8 19.9 20.0 20.0 20.0
E2-10
Motor iron loss for torque com-
pensation
W 440
508 586 750 925 1125 1260 1600 1760
E2-11
(E4-07)
Motor rated output power kW 15.00
18.50 22.00
30.00 37.00 45.00 55.00 75.00 90.00
L2-02
Momentary power loss ride
through time
sec 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
L2-03 Min. baseblock (BB) time sec 0.9 1.0 1.0 1.1 1.1 1.2 1.2 1.3 1.5
L2-04 Voltage recovery time sec 0.3 0.6 0.6 0.6 0.6 0.6 1.0 1.0 1.0
L8-02 Overheat pre-alarm level °C9598788585909098108