7-19
7
COPY
Function
CPE
ID UNMATCHED
The Inverter type or software number was
different from the stored data in the digital
operator
Use stored data of the same product (F7)
and software number (U1-14) only.
VAE
INV. KVA UNMATCH
The capacity of the Inverter and the capac-
ity of the stored data in the Digital Operator
are different.
Use stored data for the same Inverter
capacity only (o2-04).
CRE
CONTROL
UNMATCHED
The control method of the Inverter and the
control method of the stored data in the
Digital Operator are different.
Use stored data for the same control
method (A1-02).
CYE
COPY ERROR
A parameter setting written to the Inverter
was different from the setting stored in the
Digital Operator.
Retry the COPY function (o3-01 = 2)
CSE
SUM CHECK ERROR
Upon completion of the COPY function,
the Inverter’s data checksum was different
than the digital operator’s data checksum.
Retry the COPY function (o3-01 = 2)
Veri fy
Function
VYE
VERIFY ERROR
The set value of the digital operator and the
Inverter do not match
Retry the Verify function (o3-01 = 3)
Table 7.5 Digital Operator Copy Function Faults
Function
Digital Operator
Display
Probable Causes Corrective Actions