10.3 Checking Status with PMGET Instruction
10.3.1 Specifications of PMGET Instruction
Confirmation of error information
Describe UNITSEL instruction immediately before PMGET instruction, and specify the slot
and port numbers of the unit to be read.
Specify the type of data to be read (parameter or monitor information) for operand S1 of
PMGET instruction.
Store 26 words for communication parameters or 7 words for monitor information in the area
starting with the area specified by operand S2 of PMGET instruction.
10.3.2 List of Communication Parameters
Acquisition of SCU communication parameters
Operand Parameter Range Settings
[D]
Communication
mode
U0
U1
U2
U8
U9
U0: MEWTOCOL-COM
U1: MEWTOCOL7-COM
U2: MODBUS RTU
U8: General-purpose communication
U9: PLC Link
[D+1] Unit number setting U1 to U999
Unit number U1 to U999
MEWTOCOL-COM: U1 to U99
MEWTOCOL7-COM: U1 to U999
MODBUS-RTU: U1 to U247
PLC link: U1 to U16 (Default: 0)
[D+2] Baud rate setting U0 to U10
U0: 300, U1: 600, U2: 1200, U3: 2400, U4: 4800, U5:
9600, U6: 19200, U7: 38400, U8: 57600, U9: 115200,
U10: 230400 bps
[D+3] Data length setting U0 to U1 U0: 7-bit length, U1: 8-bit length
[D+4] Parity setting U0 to U2 U0: No parity, U1: Odd parity, U2: Even parity
[D+5] Stop bit length setting U0 to U1 U0: 1 bit, U1: 2 bits
10.3 Checking Status with PMGET Instruction
WUME-FP7COM-07 10-7

Table of Contents

Other manuals for Panasonic FP7 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic FP7 Series and is the answer not in the manual?

Panasonic FP7 Series Specifications

General IconGeneral
BrandPanasonic
ModelFP7 Series
CategoryController
LanguageEnglish

Related product manuals