12-5 Modbus Communication
AC10 Inverter
Reading
parameter
address
Function
Remarks
100A
Read integer power value
The integer power value is read by PC.
100B
DI terminal status
DI1~DI8—bit0~bit7
100C
Terminal output status
bit0-OUT1 bit2-fault relay
100D
AI1
0~4095 read input analog digital value
100E
AI2
0~4095 read input analog digital value
1010
Reserved
1011
Reserved
1012
Reserved
1013
Present-stage speed value
0000 : no function
0001 : stage speed 1
0010 : stage speed 2
0011 : stage speed 3
0100 : stage speed 4
0101 : stage speed 5
0110 : stage speed 6
0111 : stage speed 7
1000 : stage speed 8
1001 : stage speed 9
1010 : stage speed 10
1011 : stage speed 11
1100 : stage speed 12
1101 : stage speed 13
1110 : stage speed 14
1111 : stage speed 15
Monitoring in which stage speed inverter is.
(Valid when F500 = 1 or F500 = 2)
1014
Reserved
1015
AO1 0~100.00
Monitoring analog output percent
1016
AO2 0~100.00
Monitoring analog output percent
1017
Current speed
Monitoring current speed.
1018
Read accurate power value
Correct the power to 1 decimal place.
12.6.3 Control commands
Parameters
Address
Parameters Descriptionwrite only
2000
Command meaning:
0001Forward running (no parameters
0002Reverse runningno parameters
0003Deceleration stop
0004Free stop
0005Forward jogging start
0006Forward jogging stop
0007Fault reset
000A: Forward jogging stop