12-7 Modbus Communication
AC10 Inverter
12.7 Function Codes Related to Communication
Function Code
Function Definition
Setting Rang
Mfr’s
Value
F200
Source of start
command
0: Keypad command;
1: Terminal command;
2: KeypadTerminal;
3: MODBUS;
4: KeypadTerminalMODBUS
4
F201
Source of stop
command
0: Keypad command;
1: Terminal command;
2: KeypadTerminal;
3: MODBUS;
4: KeypadTerminalMODBUS
4
F203
Main frequency source
X
0: Digital setting memory;
1: External analog AI1;
2: External analog AI2;
3: Reserved
4: Stage speed control;
5: No memory by digital setting;
6:Reserved;
7: Reserved;
8: Reserved;
9: PID adjusting;
10: MODBUS
0
F900
Inverter Address
1~255
1
F901
Modbus Mode
Selection
1: ASCII mode
2: RTU mode
1
F903
Parity Check
0: Invalid
1: Odd
2: Even
0
F904
Baud Rate(bps)
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
3
F905
Communication
Timeout
0.0~3000.0
0.0
Set the functions code related to communication consonant with the PLC/PC communication
parameters, when inverter communicates with PLC/PC.