15-18 Parameter Reference
AC10 Inverter
Function
Code
Function
Definition
Setting Range
Mfr’s Value
Change
FA59
Emergency fire mode
0: Disabled
1: Emergency fire mode 1
2: Emergency fire mode 2
0
FA60
Running frequency of emergency fire
F112~F111
50.0
FA61
Reserved
FA62
When emergency fire control terminal is
false
0: Inverter cannot be stopped manually
1: Inverter can be stopped manually
0
×
FA63-
FA80
Reserved
Torque control parameters: FC00-FC40
Function
Code
Function
Definition
Setting Range
Mfr’s Value
Change
FC00
Speed/torque control selection
0Speed control
1Torque control
2Terminal switchover
0
FC01
Delay time of torque/speed control
switchoverS
0.01.0
0.1
FC02
Torque accel/decel time (s)
0.1100.0
1.0
FC03-
FC05
Reserved
FC06
Torque reference source
0: Digital given (FC09)
1: Analog input AI1
2: Analog input AI2
0
FC07
Torque reference coefficient
03.000
3.000
FC08
Reserved
FC09
Torque reference command value (%)
0300.0
100.0
FC10-
FC13
Reserved
FC14
Offset torque reference source
0: Digital given (FC17)
1: Analog input AI1
2: Analog input AI2
0
FC15
Offset torque coefficient
0~0.500
0.500
FC16
Offset torque cut-off frequency (%)
0~100.0
10.0
FC17
Offset torque command value (%)
0~50.0
10.0
FC18-
FC21
Reserved
FC22
Forward speed limit source
0: Digital given (FC23)
1: Analog input AI1
2: Analog input AI
0
FC23
Forward speed limit (%)
0100.0
10.0
FC24
Reverse speed limit source
0: Digital given (FC25)
1: Analog input AI1
0