9-38 Function Parameters
AC10 Inverter
F708 Trip 1 Type (Newest)
Setting range:
2: Over current (OC)
3: Over voltage (OE)
4: Input phase loss (PF1)
5: Inverter overload (OL1)
6: Under voltage (LU)
7: Overheat (OH)
8: Motor overload (OL2)
11: External malfunction (ESP)
12: Current fault before running
(Err3)
13. Tuning parameters wrong (Err2)
15: Current sampling fault (Err4)
16: Over current 1 (OC1)
17: Output phase loss (PF0)
18: Analog disconnected (Aerr)
23: PID parameters are set wrong
(Err5)
45: Communication timeout (CE)
46: Flycatching fault (FL)
49: Watchdog fault (Err6)
67: Overcurrent (OC2)
F709 Trip 2 Type
F710 Trip 3 Type
F711 Trip 1 Fault Frequency
F712 Trip 1 Fault Current
F713 Trip 1 Fault DC Bus Voltage
F714 Trip 2 Fault Frequency
F715 Trip 2 Fault Current
F716 Trip 2 Fault DC Bus Voltage
F717 Trip 3 Fault Frequency
F718 Trip 3 Fault Current
F719 Trip 3 Fault DC Bus Voltage
F720 Number of overcurrent faults
F721 Number of overvoltage faults
F722 Number of overheat faults
F723 Number of overload faults
F724 Input phase loss
(For single-phase input, set to
true)
Setting range:
0: Disabled;
1: Enabled
Mfr’s value: 1
F726 Overheat
Setting range:
0: Disabled;
1: Enabled
Mfr’s value: 1
F727 Output phase loss
Setting range:
0: Disabled;
1: Enabled
Mfr’s value: 0
F728 Input phase loss trip delay (S)
Setting range: 0.160.0
Mfr’s value: 0.5
F730 Overheat protection trip delay (S)
Setting range: 0.160.0
Mfr’s value: 5.0