9-42 Function Parameters
AC10 Inverter
Setting range: 0.000~30.00s
F813 Rotary speed loop KP1
0.01~20.00 (for 22kW and below
22kW)
1~100 (for above 22kW)
Subject to inverter
model
F814 Rotary speed loop KI1
0.01~2.00 (for 22kW and below
22kW)
0.01~10.00 (for above 22kW)
Subject to inverter
model
F815 Rotary speed loop KP2
0.01~20.00 (for 22kW and below
22kW)
1~100 (for above 22kW)
Subject to inverter
model
F816 Rotary speed loop KI2
0.01~2.00 (for 22kW and below
22kW)
0.01~10.00 (for above 22kW)
Subject to inverter
model
F817 PID switching frequency 1
F818 PID switching frequency 2
Figure 9-14 PID parameter
Dynamic response of vector control speed can be adjusted through adjusting gains of speed
loop. Increasing KP and KI can speed up dynamic response of speed loop. However, if
proportional gain or integral gain is too large, it may give rise to oscillation.
Recommended adjusting procedures:
Make fine adjustment of the value starting from the manufacturer value if the manufacturer
setting value cannot meet the needs of practical application. Be cautious that amplitude of