POWER WIRING INSTALLATION NOTES
D
D
A---5
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 Rev . N 013004
Table E. Ratings & External Wiring Requirements for
Po werwar e 9330 (10 kVA---20 kV A)
Options Cabinet OUTPUT Transformer
Ratings 50/60 Hz
Basic unit ratings at Voltage
Conductor
0.7 lagging PF load
Series/
Model
kVA/KW
Input Output
u
pu
Current
(Amps)
Minimum
Size
20/10 9.5/6.65 208/220 208 26.4 10
COut
ut from
20/10 9.5/6.65 208/220 480 11.4 14
AC
Output Transformer
20/15 14.25/10 208/220 208 39.6 8
OUTPUT
to Critical Load
0.95min.PF
20/15 14.25/10 208/220 480 17 12
.
.
3, 1 Neutral, 1 gnd
20/20 19/13.3 208/220 208 52.7 6
20/20 19/13.3 208/220 480 22.8 10
Table F. Ratings & External Wiring Requirements for
Po werwar e 9330 (10 kVA---20 kV A)
Options Cabinet OUTPUT Without Output Transformer
Ratings 50/60 Hz
Basic unit ratings at Voltage
Conductor
0.7 lagging PF load
Series/
Model
kVA/KW
Input Output
u
pu
Current
(Amps)
Minimum
Size
AC Outp u t fr om Out p u t 20/10 10/7 208/220 208/220 27.8 8
OUTPUT
to Critical Load
20/15 15/10.5 208/220 208/220 41.6 6
.
m
n.
3, 1 Neutral, 1 gnd
20/20 20/14 208/220 208/220 55.5 4