POWER WIRING INSTALLATION NOTES
164201300---1
A --- 1 6
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 Rev . N 013004
Table U. Power Cable Conduit Requirements Powerware 9330 (35 kVA--40 kVA)
Powerware
System
Voltage Terminal
Number of
Wires in
Conduit
Minimum
Conduit
Trade Size
(inches)
Number of
Conduits
AC Input to UPS
(A,B,C,Gnd)
4 1-1/4 1
9330-40/35
208/220
AC
AC Input to Bypass
(A,B,C,Neut,Gnd)
5 2 1
Output
(A,B,C,Neut,Gnd)
5 2 1
AC Input to UPS
(A,B,C,Gnd)
4 1 1
9330---40/35
480
AC
AC Input to Bypass
(A,B,C,Neut,Gnd)
5 1 1
Output
(A,B,C,Neut,Gnd)
5 1 1
AC Input to UPS
(A,B,C,Gnd)
4 3/4 1
9330---40/35
600
AC
AC Input to Bypass
(A,B,C,Neut,Gnd)
5 3/4 1
Output
(A,B,C,Neut,Gnd)
N/A N/A N/A
9330---40/35
288
DC
External Battery DC Source
(Positive, Negative, Gnd)
3 1 1
AC Input to UPS
(A,B,C,Gnd)
4 1-1/2 1
9330-40/40
208/220
AC
AC Input to Bypass
(A,B,C,Neut,Gnd)
5 2 1
Output
(A,B,C,Neut,Gnd)
5 2 1
AC Input to UPS
(A,B,C,Gnd)
4 3/4 1
9330-40/40
480
AC
AC Input to Bypass
(A,B,C,Neut,Gnd)
5 1 1
Output
(A,B,C,Neut,Gnd)
5 1 1
AC Input to UPS
(A,B,C,Gnd)
4 3/4 1
9330-40/40
600
AC
AC Input to Bypass
(A,B,C,Neut,Gnd)
5 3/4 1
Output
(A,B,C,Neut,Gnd)
N/A N/A N/A
9330---40/40
288
DC
External Battery DC Source
(Positive, Negative, Gnd)
3 1-1/4 1