A --- 3 1
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 Rev . N 013004
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVI SION:
L
ONELINE DRAWINGS OF UPS SYSTEM
1of1
041503
UPS CABINET
INVERTER
RECTIFIER
CB1
ST ATIC
SWITCH
BACKF EED
CONTACTOR
(K5)
R S --- 2 3 2
REMOTE EPO
BUILDING ALARMS
COMMUNICATIONS
SERVER
AC OUTPUT
TO
CRITICAL LOAD
OUTPUT
CONTACTOR
OUTPUT FILTER
(K3)
D
C
AC INPUT TO
UPS RECTIFIER
3 W I R E A --- B --- C
AC INPUT
TO BYPASS
4 W I R E A --- B --- C
ROTATION
ROTATION
SEENOTE1
BA
NOTE 1: Remove jumper for dual feed.
(See Tables X, Y, and Z )
INPUT FIL TER
OPTIONAL
UPS SYSTEM WITH 208V/220V INPUT AND 208V/220V OUTPUT,
SINGLE OR DUAL FEED
POWERWARE 9330 (10 kVA---20 kVA)
POWERWARE 9330 (25 kVA---40 kVA)
INPUT
CONTACTOR
(K1)
BATTERY
SWITCHES
INTERNAL
BATTERY
DC--- DC
CONVERTER
(K2)
BATTERY
CABINET
EXTERNAL
BATTERY
BATTERY
BREAKER
BATTERY
BREAKER
GENERAL
PURPOSE RELAYS
CAN INTERFACE
X-SLOT
INTERFACE
(Optional)
164201300---6
MAINTENANCE
BYPASS
SWITCH
(DUAL FEED)
AC INPUT TO
UPS RECTIFIER
(SINGLE OR DUAL FEED)
(SINGLE FEED)
CB2
FUSE
FUSE
REMOTE
BATTERY
INPUT
E1, E2, E3 E6, E7, E8, E12
E9, E10,
E11, E12
E4. E5