NOTICE!
Do not supply with voltage
For the connection of an external semi-conductor or mechanical switch.
mA Output
Current range: 0/3.8 – 23 mA
In the event of a fault: 3.6 or 21.5 mA
Max. apparent ohmic resistance:
450 W at 20.5 mA
Max. output voltage: 18 V DC
Overvoltage-resistant up to: ± 30 V
Output accuracy: ± 0.25 % of range
Galvanically isolated from all other connections (500 V)
Pump activation
Max. switching voltage: 50 V (protective low voltage)
Max. switching current: 50 mA
Max. residual current (open):
10 m A
Max. resistance (closed):
60 W
Max. switching frequency (HW) at 50%
filling factor
500 Hz
Electrical Data