10 - Function Test
Solenoid moistening Y3
0 - 1
Activation of solenoid valve
moistening Y3
13 - Function Test
Drain Valve Motor M7
Direction 1 -2
End switch S12 1 - 0
Direction 1: Clockwise
Direction 2: Counter clockwise
14 - Function Test
CO
2
measurement
Gas Steam Blower
Min - Start - Max
CO2 FC rpm
List 5,25µA xxx
Gas blower Steam:
- Reference CO2 values ONLY to
list in training manual
„valid since April, 2005“!
- CO
2
adjustment with CO
2
screw
on gas valve at Max rpm only.
- CO
2
too high:
turn CO
2
screw 2 turns clockw.,
than counter clockw. until CO
2
value correct;
- CO
2
too low:
- turn CO
2
screw counter clockw.
until CO
2
value correct;
- check CO
2
at Min rpm
- CO value must be always below
300 ppm!
- Flame current should be always
above 3,00 µA, idealy 4,0-5,75 µA
12 - Function Test
CleanJet Pump M6
0 - 1
Activation of CleanJet Pump M6
16 - Function Test
CO
2
measurement
Gas Hot Air Blower Bottom
Min - Start - Max
CO2 FC rpm
List 5,25µA xxx
Gas blower Hot Air bottom
- Reference CO2 values ONLY to
list in training manual
„valid since April, 2005“!
- CO
2
adjustment with CO
2
screw
on gas valve at Max rpm only.
- CO
2
too high:
turn CO
2
screw 2 turns clockw.,
than counter clockw. until CO
2
value correct;
- CO
2
too low:
- turn CO
2
screw counter clockw.
until CO
2
value correct;
- check CO
2
at Min rpm
- CO value must be always below
300 ppm!
- Flame current should be always
above 3,00 µA, idealy 4,0-5,75 µA
11 - Function Test
Humidity fl ap motor M3
0 - 1
End switch S4 1 - 0
S4 shows 1 = Flap closed
S4 shows 0 = Flap open
15 - Function Test
CO
2
measurement
Gas Hot Air Blower Top
Min - Start - Max
CO2 FC rpm
List 5,25µA xxx
Gas blower Hot Air top
- Reference CO2 values ONLY to
list in training manual
„valid since April, 2005“!
- CO
2
adjustment with CO
2
screw
on gas valve at Max rpm only.
- CO
2
too high:
turn CO
2
screw 2 turns clockw,
than counter clockw. until CO
2
value correct;
- CO
2
too low:
- turn CO
2
screw counter clockw.
until CO
2
value correct;
- check CO
2
at Min rpm
- CO value must be always below
300 ppm!
- Flame current should be always
above 3,00 µA, idealy 4,0-5,75 µA
Start
Start
Start
Start
Start
Start
Start
Function test