Chapter 3 Application Examples RIGOL
DP800 Programming Guide 3-5
To Use the Monitor
Requirement
Use the SCPI commands to realize the following functions:
Monitor CH1.
Set the monitor condition: >Volt, >Curr or >Power; set the voltage to 5V, the current to 3A and the
power to 15W; set the stop mode to OutpOff, Warning and Beeper.
Enable the monitor.
Method
1 *IDN? /*Query the ID character string of the power supply to check whether
the remote communication is normal*/
2 :INST CH1 /*Select CH1*/
3 :MONI:VOLT:COND >V,OR /*Set the voltage monitor condition to >Voltand the logic relation to
OR*/
4 :MONI:VOLT 5 /*Set the voltage of the monitor condition to 5V*/
5 :MONI:CURR:COND >C,OR /*Set the current monitor condition to “>Currand the logic relation to
OR*/
6 :MONI:CURR 3 /*Set the current of the monitor condition to 3A*/
7 :MONI:POWER:COND >P /*Set the power monitor condition to “>Power*/
8 :MONI:POWER 15 /*Set the power of the monitor condition to 15W*/
9 :MONI:STOP OUTOFF,ON /*Enable the OutpOffstop mode*/
10 :MONI:STOP WARN,ON /*Enable the Warningstop mode*/
11 :MONI:STOP BEEPER,ON /*Enable the Beeperstop mode*/
12 :MONI ON /*Enable the monitor*/

Table of Contents

Other manuals for Rigol DP832

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rigol DP832 and is the answer not in the manual?

Rigol DP832 Specifications

General IconGeneral
Number of Outputs3
Output Voltage Range CH1/CH20-30V
Output Voltage Range CH30-5V
Output Current Range CH1/CH20-3A
Output Current Range CH30-3A
Total Power195 W
Power per Channel CH1/CH290 W
Power per Channel CH315 W
Voltage Resolution1 mV
Current Resolution1 mA
InterfacesUSB, RS232
Display3.5 inch TFT LCD

Related product manuals