1769-IF8 Process Alarms
Process alarms alert you when the module has exceeded configured high or 
low limits for each channel. You can latch process alarms. These are set at 
two user configurable alarm trigger points:
• Process Alarm High
• Process Alarm Low
Each input channel’s process alarms are controlled by bits in the 
Configuration Data file. Enable alarms for a channel by setting (1) the EA bit 
for that channel. Set the AL bit (1) for a channel to enable the alarm latching.
Each channel’s process alarm high data value and process alarm low data value 
are set by entering values in the corresponding words of the Configuration 
Data file for that channel.
The values entered for a channel’s process alarm data values must be within 
the normal operating data range as set by the input Data Format selected for 
that channel. If a process alarm data value is entered that is outside the normal 
operating data range set for a channel, the module indicates a configuration 
error.