Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules        4-11
1769-OF2 Fault Value (Channel 0 and 1)
Using words 2 and 4 for channels 0 and 1, you can specify the values the 
outputs will assume when the system enters the fault mode. The default value 
is 0. Valid values are dependent upon the range selected in the range selection 
field. If the value you entered is outside the normal operating range for the 
output range selected, the module generates a configuration error. 
For example, if you select engineering units for the ±10V dc range and enter a 
fault value within the normal operating range (0 to 10000), the module will 
configure and operate correctly. However, if you enter a value outside the 
normal operating range (for example 11000), the module indicates a 
configuration error.
1769-OF2 Program/Idle Value (Channel 0 and 1)
Use words 3 and 5 to set the integer values for the outputs to assume when the 
system enters the program mode. The values are dependent upon the range 
selected in the range selection field. If the value you entered is outside the 
normal operating range for the output range selected, the module generates a 
configuration error. The default value is 0.
TIP
Not all controllers support this function. Refer to your 
controller’s user manual for details.
TIP
Not all controllers support this function. Refer to your 
controller’s user manual for details.