Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Input Modules 3-13
Effective Resolution
The effective resolution for an input channel depends upon the filter
frequency selected for that channel. The following tables provide the effective
resolution for the four frequencies for each of the range selections.
Table 3.8 50Hz / 60Hz Effective Resolution
1769-IF4
Input
Range
Raw/Proportional Data
Over the Full Input Range
Engineering Units Over
the Full Input Range
Scaled-For-PID Over
the Full Input Range
Percent
Over the Full Input
Range
Bits and
Engineering
Units
Resolution
Decimal
Range and
Count Value
Resolution Decimal
Range
and
Count
Value
Resolution Decimal
Range
and
Count
Value
Resolution Decimal
Range
and
Count
Value
-10 to
+10V dc
Sign +14
0.64 mV/
2 counts
±32767
Count by 2
1.00 mV/
1 count
±10500
Count by 1
1.22 mV/
1 count
-410 to
+16793
Count by 1
Not
Applicable
Not
Applicable
0 to +5V dc Sign +13
0.64 mV/
4 counts
-3121 to
+32767
Count by 4
1.00 mV/
1 count
-500 to
+5250
Count by 1
0.92 mV/
3 counts
-1638 to
+17202
Count by 3
1.00 mV/
2 counts
-1000 to
+10500
Count by 2
0 to +10V dc Sign +14
0.64 mV/
2 counts
-1560 to
+32767
Count by 2
1.00 mV/
1 count
-500 to
+10500
Count by 1
1.22 mV/
2 counts
-819 to
+17202
Count by 2
1.00 mV/
1 count
-500 to
+10500
Count by 1
+4 to
+20 mA
Sign +14
1.28 µA/
2 counts
+4993 to
+32767
Count by 2
2.00 µA/
2 counts
+3200 to
+2100
Count by 2
1.95 µA/
2 counts
-819 to
+17407
Count by 2
1.60 µA/
1 count
-500 to
+10625
Count by 1
+1 to +5V dc Sign +13
0.64 mV/
4 counts
+3121 to
+32767
Count by 4
1.00 mV/
1 count
+500 to
+5250
Count by 1
0.73 mV/
3 counts
-2048 to
+17407
Count by 3
0.80 mV/
2 counts
-1250 to
+10625
Count by 2
0 to +20 mA Sign +14
1.28 µA/
2 counts
0 to +32767
Count by 2
2.00 µA/
2 counts
0 to
+21000
Count by 2
2.44 µA/
2 counts
0 to
+17202
Count by 2
2.00 µA/
1 count
0 to
+10500
Count by 1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation 1769-IF4 and is the answer not in the manual?

Rockwell Automation 1769-IF4 Specifications

General IconGeneral
BrandRockwell Automation
Model1769-IF4
CategoryI/O Systems
LanguageEnglish

Related product manuals