Publication 1769-UM002B-EN-P - July 2005
Installation and Wiring 2-11
System Wiring Guidelines
Consider the following when wiring your system:
General
All module commons (ANLG COM) are connected in the analog
module. The analog common (ANLG COM) is not connected to earth
ground inside the module.
Channels are not isolated from each other.
Do not use the analog modules NC terminals as connection points.
To ensure optimum accuracy, limit overall cable impedance by keeping
your cable as short as possible. Locate the I/O system as close to your
sensors or actuators as your application will permit.
Use Belden™ 8761, or equivalent, shielded wire.
Keep shield connection to ground as short as possible.
Under normal conditions, the drain wire and shield junction must be
connected to earth ground via a panel or DIN rail mounting screw at
the analog I/O module end.
(1)
1769-IF4 and -IF8 Input Modules
If multiple power supplies are used with analog inputs, the power supply
commons must be connected together.
The 1769-IF4 and -IF8 modules do not provide loop power for analog
inputs. Use a power supply that matches the input transmitter
specifications.
Differential analog inputs are more immune to noise than single-ended
analog inputs.
Voltages on Vin+, V/Iin-, and Iin+ of the 1769-IF4 and -IF8 modules
must be within ±10V dc of analog common.
1769-OF2, -OF8C, and -OF8V Output Modules
Voltage outputs (Vout 0+ and Vout 1+ for 1769-OF2, Vout 0+
through Vout 7+ for 1769-OF8V) of the output modules are referenced
to ANLG COM. Load resistance for a voltage output channel must be
equal to or greater than 1K .
Current outputs (Iout 0+ and Iout 1+ for 1769-OF2, Iout 0+ through
Iout 7+ for 1769-OF8C) of the output modules source current that
returns to ANLG COM. Load resistance for a current output channel
must remain between 0 and 500 .
(1)
In environments where high-frequency noise may be present, it may be necessary to directly ground cable
shields to earth at the module end and via a 0.1µF capacitor at the sensor end.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation 1769-IF4 and is the answer not in the manual?

Rockwell Automation 1769-IF4 Specifications

General IconGeneral
BrandRockwell Automation
Model1769-IF4
CategoryI/O Systems
LanguageEnglish

Related product manuals