Publication 1769-UM002B-EN-P - July 2005
Module Data, Status, and Channel Configuration for the Output Modules        4-15
1769-OF2 Module 
Resolution
The resolution of an analog output channel depends on the output type/range 
and data format selected. Table 4.6 provides detailed resolution information 
for the 1769-OF2.
Table 4.6 1769-OF2 Output Resolution
1769-OF
2 Output 
Range
Raw/Proportional Data 
Over the Full Input Range
Engineering Units Over 
the Full Input Range
Scaled-For-PID Over the 
Full Input Range
Percent
Over the Full Input Range
Bits and 
Engineering 
Units 
Resolution
Decimal 
Range 
and Count 
Value
Resolution Decimal 
Range 
and Count 
Value
Resolution Decimal 
Range 
and Count 
Value
Resolution Decimal 
Range and 
Count 
Value
-10 to 
+10V dc
Sign +14
0.64 mV/
2 counts
±32767
Count by 2
2.00 mV/
2 counts
±10500
Count by 2
2.44 mV/
2 counts
-410 to 
+16793
Count by 2
Not 
Applicable
Not 
Applicable
0 to 
+5V dc
Sign +13
0.64 mV/
4 counts
-3121 to 
+32767
Count by 4
2.00 mV/
2 counts
-500 to 
+5250
Count by 2
0.92 mV/
3 counts
-1638 to 
+17202
Count by 3
1.00 mV/
2 counts
-1000 to 
+10500
Count by 2
0 to 
+10V dc
Sign +14
0.64 mV/
2 counts
-1560 to 
+32767
Count by 2
2.00 mV/
2 counts
-500 to 
+10500
Count by 2
1.22 mV/
2 counts
-819 to 
+17202
Count by 2
2.00 mV/
2 counts
-500 to 
+10500
Count by 2
+4 to 
+20 mA
Sign +14
1.28 µA/
2 counts
+4993 to 
+32767
Count by 2
2.00 µA/
2 counts
+3200 to 
+2100
Count by 2
1.95 µA/
2 counts
-819 to 
+17407
Count by 2
3.20 µA/
2 counts
-500 to 
+10625
Count by 2
+1 to
+5V dc
Sign +13
0.64 mV/
4 counts
+3121 to 
+32767
Count by 4
2.00 mV/
2 counts
+500 to 
+5250
Count by 2
0.73 mV/
3counts
-2048 to 
+17407
Count by 3
0.80 mV/
2 counts
-1250 to 
+10625
Count by 2
0 to 
+20 mA
Sign +14
1.28 µA/
2 counts
0 to 
+32767
Count by 2
2.00 µA/
2 counts
0 to 
+21000
Count by 2
2.44 µA/
2 counts
0 to 
+17202
Count by 2
4.00 µA/
2 counts
0 to +10500
Count by 2