Chapter 6 Troubleshoot the System
Alert 2056 Cannot copy recipe to a loaded application. Unload application and try again.
Alert 2057
Terminal is running low on application memory
(<Available_Virtual_Memory>bytes).
Reset the terminal or this may lead to fatal error.
Alert 2058
Failed setting property: /*S:0 Param1*/::/*S:0 Param2*/, value =
/*S:0 Param3*/
Verify the range of the numeric display that uses the external tag as
its write tag is within the range of a tag (validation should provide a
warning if the range of the tag is greater than the range of a numeric
entry). Make sure that the values of the state based objects that write
to an external tag are within the range of the tag. Make sure that the
value that written to an external tag matches the tag type (for
example, do not write a non-numeric string into a numeric tag).
Make sure the Ethernet port is enabled.
Alert 2059
Failed setting property (/*S:0 Param1*/): /*S:0 Param2*/::/*S:0
Param3*/, value = /*S:0 Param4*/
Verify the range of the numeric display that uses the external tag as
its write tag is within the range of a tag (validation should provide a
warning if the range of the tag is greater than the range of a numeric
entry). Make sure that the values of the state based objects that write
to an external tag are within the range of the tag. Make sure that the
value that written to an external tag matches the tag type (for
example, do not write a non-numeric string into a numeric tag).
Alert 2060 Terminal is running low on RAM (<Available_RAM>bytes). Reset the terminal or this may lead to fatal error.
Alert 2061 Out of memory: Terminal cannot continue to run and will be reset.
This is a out of memory critical message. Dismissing this dialog
causes the terminal to reset.
After the terminal resets, try to edit an application and reduce its size
by removing some objects, for example, user controls, screens, tags,
or alarms.
Alert 2062 Cannot copy recipe to a loaded application. Unload application and try again.
Alert 2064 Cannot enter Safe Mode while terminal security is enabled. Disable terminal security and try again.
Alert 2065 Table has changed. Do you want to continue? Press Yes to continue with the changed Recipe table.
Alert 2066 Logging Error
Make sure a microSD card or USB device is connected to the terminal
to store the datalog.
Alert 2067 Invalid filename Make sure filename is valid.
Alert 2068 Only one Trend with data logging is allow Make sure the application only has one Trend with data logging.
Alert 2069 Landscape Orientation. Confirm Restart? Select No to restart later.
Alert 2070 Portrait Orientation. Confirm Restart? Select No to restart later.
Alert 2071
Application was designed for a different Orientation and may not
appear or operate as intended. Continue?
Press Yes to continue, or No to cancel. Then change the orientation
of the application in Connected Components Workbench software to
match the terminal and try again.
Alert 2072
Application was designed for a different Platform type and
Orientation, and may not appear or operate as intended.
Continue?
Press Yes to continue, or No to cancel. Then change the catalog of
the application in Connected Components Workbench software to
match the terminal and try again.
Alert 2073
Non-validated application is not supported for CompactLogix
controller. Validate before loading
Validate the application and correct any validation errors, save the
application, then try again.
Alert 2074 Terminal encountered an exception and will reboot
This message is for informational purposes. No corrective action
needed.
Alert 2075 Application will be unloaded. Confirm (Y/N)? Press Yes to unload the application.
Alert 2076
This application does not have at least one Goto Config button. Set
as Startup Application?
Press Yes to continue setting the application as a startup application,
or No to cancel. Edit the application and make sure there is at least
one Goto Config button.
Alert 2077 Controller Settings cannot be changed for running application. Stop the application and try again.
Alert 2078
Controller address cannot conflict with PanelView 800 terminal
Station Address.
Make sure the controller address is different from the PanelView 800
terminal station address.
Alert 2079
CompactLogix controller based application must contain valid
path.
Make sure a valid path exists and try again.
Alert 2080
Invalid View-Only password. Password should not contain any
special character.
Make sure the View-Only password does not contain any special
characters.
Alert 2081 Old password does not match with terminal. Make sure the correct password is entered in the Old Password field.
Alert 2082 VNC Server error. Restart the terminal and try again.
Alert 2083
Controller address cannot be larger than PanelView 800 terminal
Max Node('31').
Make sure the address of the controller is smaller than the maximum
node of PanelView 800 terminal(’31’).
Alert 2084 Password cannot be empty. Enter valid password.
Alert 2085 Enable Ethernet port. Confirm Restart? Press Yes to restart the terminal.
Alert 2086 Disable Ethernet port. Confirm Restart? Press Yes to restart the terminal.
PanelView 800 Terminal Alerts (Continued)
Category ID Description Corrective Action