Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 101
Chapter 6 Troubleshoot the System
Troubleshooting If your terminal does not startup correctly, check for adequate power, observe
the splash screen state message and status code, indicator states, or an
application that is not running during power-up.
Determine what changed since the last time the terminal ran normally and
decide if the change can be reversed.
Check for Adequate Power
A terminal that does not receive adequate power could cause unpredictable
behavior. Verify the power requirements in the Specifications table.
Alert 2087 Enable Serial port. Confirm Restart? Press Yes to restart the terminal.
Alert 2088 Disable Serial port. Confirm Restart? Press Yes to restart the terminal.
Alert 2089 Cannot disable both communication port. Make sure at least one communication port is enabled.
Alert 2090 Invalid Control password. Password must contain at least one special character.
Alert 2091 VNC Server is Disabled. Enable VNC Server to change/reset password.
Alert 2092 Ethernet port is disabled. Go to Port Settings on the terminal to enable the Ethernet port.
Alert 2093 Serial port is disabled. Go to Port Settings on the terminal to enable the Serial port.
Alert 2094 Existing VNC client connection will be terminated. Confirm (Y/N)? Press Yes to terminate the VNC connection, or No to cancel.
Alert 2095 Cannot edit recipe for running application. Unload the application and try again.
Alert 2096 Recipe with the same name already exists Make sure the recipe name is unique.
Alert 2097
Recipe Name cannot contain more than 31 characters. Choose
another name.
Make sure the recipe name does not exceed 31 characters.
Alert 2098
The Name cannot be blank and must contain only alphanumeric
characters plus [ $'@!()_- ].
Make sure the name contains only alphanumeric characters plus
[ $'@!()_- ].
Alert 2099
Deletion of a recipe in a design secured application is not allowed.
See Copy or Edit Recipes
on page 22.
Make sure the application is not design secured.
Alert 2100
Renaming of a recipe in a design secured application is not
allowed. See Copy or Edit Recipes
on page 22.
Make sure the application is not design secured.
Alert 3001 Available memory is too low to run the application. Try to release some memory or this may lead to fatal error.
Multilanguage 8193
Language switch ignored. Application was not configured with
new language. An attempt was made to switch to a language that
is not configured for this application.
Either add the specified language and associated strings or remove
the unconfigured language selection.
PanelView 800 Terminal Alerts (Continued)
Category ID Description Corrective Action

Table of Contents

Other manuals for Rockwell Automation Allen-Bradley PanelView 800 HMI

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley PanelView 800 HMI and is the answer not in the manual?

Rockwell Automation Allen-Bradley PanelView 800 HMI Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley PanelView 800 HMI
CategoryTouch terminals
LanguageEnglish

Related product manuals