98 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021
Chapter 6 Troubleshoot the System
Recipe 1019
Recipe /*S:0 Param1*/ failed. Cause: No recipe selected in
Selector.
Select recipe and try again.
Recipe 1020
Recipe /*S:0 Param1*/ failed. Cause: Data type of data point /
*S:0 Param2*/ is incompatible with ingredient type of ingredient /
*S:0 Param3*/.
Change the type of the ingredient to match the type of the data point,
or select a different data point which matches the type of the
ingredient.
Recipe 1021
Recipe /*S:0 Param1*/ failed. Cause: Unable to read from /*S:0
Param2*/
Check the communication settings, and data point specification.
Recipe 1022 Recipe /*S:0 Param1*/ failed. Cause: Unable to read from Tag. Check the communication settings, and data point specification.
Recipe 1023
Recipe download failed. Cause: The value /*S:0 Param1*/ is
greater than the maximum value /*S:0 Param2*/ allowed for
ingredient /*S:0 Param3*/
Correct the dataset value.
Recipe 1024
Recipe /*S:0 Param1*/ failed. Cause: Table does not contain a
recipe.
Restore the recipe in the table before doing a save operation.
Recipe 1025
Recipe /*S:0 Param1*/ of recipe /*S:0 Param2*/failed. Cause: ยท
Recipe file not accessible.
Try to reload the application to see if the recipe is still there, or
restore from a .cha file from your computer or SD card.
Recipe 1026 Recipe Upload Failed.
This message is for informational purposes. No corrective action
needed.
Recipe 1027 Recipe operation in progress.
This message is for informational purposes. No corrective action
needed.
Alert 2000 Loading.
This message is for informational purposes. No corrective action
needed.
Alert 2001 Unloading.
This message is for informational purposes. No corrective action
needed.
Alert 2002 Terminal is starting up...
This message is for informational purposes. No corrective action
needed.
Alert 2003 Application is currently being edited, user input is disabled. Put the application into Test or Run mode to enable user input.
Alert 2004 Copying file...
This message is for informational purposes. No corrective action
needed.
Alert 2005 Deleting file...
This message is for informational purposes. No corrective action
needed.
Alert 2006 Operation failed.
This message is for informational purposes. No corrective action
needed.
Alert 2007 Operation succeeded.
This message is for informational purposes. No corrective action
needed.
Alert 2008 Cannot run application. Application version incompatible.
Edit, validate, and then save the application with this version and try
again.
Alert 2009
Cannot run application. Communication connection not
supported.
Terminal does not support the communication connection
configured in this application. Edit the application and configure
communication for the supported connection type.
Alert 2010
This application is not validated. Are you sure you want to run a
non-validated application?
If you do not want to run the invalid application, cancel the operation,
then edit and validate the application. Correct all validation errors,
save the application, and try again.
Alert 2011 Cannot run a modified application. Save the application and try again.
Alert 2012 Application has been modified. Continue without saving?
Edit the application and save prior to performing this operation,
otherwise changes to the application may be lost.
Alert 2013
Currently loaded application has been modified. All changes will
be lost by running this application. Continue?
Edit the application and save prior to performing this operation,
otherwise changes to the application may be lost.
Alert 2014
Application was designed for a different terminal type and may
not appear or operate as intended. Continue?
Edit the application on the terminal type that it is intended for.
Alert 2015 Application will be unloaded and deleted. Continue? Click Yes to continue with operation.
Alert 2016 Confirm deletion? Click Yes to delete the file.
Alert 2017 Confirm restart? Press Yes to restart the terminal.
Alert 2018 File already exists. Overwrite?
If you do not want to overwrite the file, cancel the operation and
rename the file before performing this operation.
Alert 2019
Cannot copy over loaded application. Unload application and
continue with overwrite?
Click OK to unload and overwrite the application.
Alert 2020 Cannot copy over loaded application. Unload application and try again.
Alert 2021 Insufficient space to complete file copy. Remove files to free space from the destination and try again.
Alert 2022 Source and destination cannot be the same. Verify the source and destination are not the same and retry.
PanelView 800 Terminal Alerts (Continued)
Category ID Description Corrective Action