NexU
INSTALLATION MANUAL
If two powered units are in between more than one non
compulsory to split power in the circuit.
UDat No. 2
Note: As CAN bus is a bus for industrial applications, it is protected against parasites and
other perturbations that may exist in a garage. Nevertheless, to have a good function, the
following rules must be respected:
-
Do always connect the armours/shie
line.
-
The network cables must not be placed near or parallel with
power supplies or
crossing of these cables, this must be done in a 90º angle.
-
If the power supply cable and network cable must go in the same way,
these must be separated with the power cable at one side and the
network cable at the other.
-
Do never connect the power to an equipment without first have
checked that the earth cabling i
UDat 1
Bus In
INSTALLATION MANUAL
If two powered units are in between more than one non
-
externally powered unit, it is
compulsory to split power in the circuit.
In this case, UValve and UMeter are powered up by
Note: As CAN bus is a bus for industrial applications, it is protected against parasites and
other perturbations that may exist in a garage. Nevertheless, to have a good function, the
following rules must be respected:
Do always connect the armours/shie
lds
in the two endpoints of the
The network cables must not be placed near or parallel with
power supplies or
power supply cables
; If it is not possible to avoid the
crossing of these cables, this must be done in a 9angle.
If the power supply cable and network cable must go in the same way,
these must be separated with the power cable at one side and the
network cable at the other.
Do never connect the power to an equipment without first have
checked that the earth cabling i
s done correctly.
UDat 1
Bus Out
UDat 2
Rev 3 (XXXX 2019)
40
externally powered unit, it is
In this case, UValve and UMeter are powered up by
Note: As CAN bus is a bus for industrial applications, it is protected against parasites and
other perturbations that may exist in a garage. Nevertheless, to have a good function, the
in the two endpoints of the
The network cables must not be placed near or parallel with
the
; If it is not possible to avoid the
crossing of these cables, this must be done in a 90º angle.
If the power supply cable and network cable must go in the same way,
these must be separated with the power cable at one side and the
Do never connect the power to an equipment without first have
s done correctly.