Installation manual
HB-37350-810-01-50F-EN PSC1-C-10 Installation manual V2.1.docx Page 53 of 189
Version: 50F
4.2.1.4.3 Dual-channel sensor without time monitoring and without cross-circuit testing
Faults are detected as a minimum on demand. The DC is medium and can be changed to the
high category by using cyclic tests (start tests, operative/organisational tests) depending on
the test frequency.
For this purpose only normally closed contacts are to be used for safety applications.
PL d according to EN ISO 13849-1 can be achieved on the usage of sensors / switching
elements with fault exclusion for the failure of the switching contacts to open. This exclusion is
allowed on the usage of positively opening switches with correct positive actuation. It is also
allowed to use sensors with self-monitoring output contacts.
PL e according to EN ISO 13849-1 can be achieved on the usage of diverse sensors / input
elements with an adequately high MTTF
d
in conjunction with plausibility monitoring of the
timing and an adequately high change in switching state = dynamic testing.
I00
I01
I02
I03
T0
T1
X14
.
.
.
L+
L-
X12
Homogeneous dual-channel sensor without test pulses, with positive opening
I00
I01
I02
I03
T0
T1
X14
.
.
.
L+
L-
X12
S1
A1
Diverse dual-channel input element, without test pulses
Safety instructions:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the schmersal PSC1-C-10 Series and is the answer not in the manual?

schmersal PSC1-C-10 Series Specifications

General IconGeneral
Brandschmersal
ModelPSC1-C-10 Series
CategoryControl Unit
LanguageEnglish

Related product manuals