Electrical installation
Terminal assignment and DIP switches
Manual – DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
28
Assignment
No. Name Function
X26 1 CAN1H System bus CAN1 high
2 CAN1L System bus CAN 1low
3 DGND Reference potential for controller/CAN1
4 Reserved –
5 Reserved –
6 DGND Reference potential for controller/CAN1
7 DC24V Voltage supply controller
6.2.3 X30-1/X30-2: Ethernet3/Ethernet4 connection
Function
Connection to Ethernet network
INFORMATION
• According to IEC 802.3, the maximum cable length for 10/100 MBaud Ethernet
(10BaseT/100BaseT), e.g. between 2network stations, is 100m.
• SEW‑EURODRIVE recommends that you do not directly connect third-party end
devices to the DHR21B/41B option in order to minimize the load on the end
devices in EtherNet/IP networks caused by undesired multicast data traffic. Con-
nect devices from third-party manufacturers via a network component that sup-
ports the IGMP snooping functionality (e.g. managed switch). Managed switches
with IGMP snooping functionality are not required for PROFINETIO and Modbus/
TCP networks.
Connection type
To connect DHR21B/41B to the Ethernet network, connect Ethernet interface X30-1
or X30-2 (RJ45 plug connector) to the other network stations using a category5,
classD twisted-pair cable in accordance with IEC11801 edition2.0. The integrated
switch assists you in implementing a line topology and provides auto-crossing func-
tions.
Assignment
No. Name Function
X30-1 Ethernet 3
Ethernet default assignment
X30-2 Ethernet 4