6
Electrical installation
Terminal assignment and DIP switches
Manual – DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
33
6.2.6 X31: Digital inputs and outputs
Function
The terminal X31 provides eight digital inputs/outputs (e.g. for controlling external ac-
tuators/sensors).
Connection type
Spring terminal plug connector
Wiring diagram
Assignment
No. Name Function
X31 1 +24V input DC24V voltage supply
2 REF24V Reference potential for binary signals
3 DIO0 Digital input/output (DIO0)
4 DIO1 Digital input/output (DIO1)
5 DIO2 Digital input/output (DIO2)
6 DIO3 Digital input/output (DIO3)
7 DIO4 Digital input/output (DIO4)
8 DIO5 Digital input/output (DIO5)
9 DIO6 Digital input/output (DIO6)
10 DIO7 Digital input/output (DIO7)
Binary inputs
• The digital inputs are electrically isolated by optocouplers.
• The permitted input voltages are defined according to IEC61131.
+13V–+30V = "1" = contact closed
-3V–+5V = "0" = contact open
Binary outputs
• The digital outputs are electrically isolated by optocouplers.
• The digital outputs are short-circuit proof but not external-voltage-proof.
• The maximum permitted output current is 150mA per digital output. All eight digital
outputs can be operated simultaneously with this current.
22900055/EN – 08/2016