Electrical installation
Terminal assignment and DIP switches
Manual – DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
34
NOTICE
The supply voltage must be present on X31:1/2 for using the digital inputs and out-
puts.
Overvoltage may damage the DH.21/41B controller. In this case, the specified func-
tion of the digital inputs and outputs is no longer ensured.
• To prevent dangerous voltage peaks from occurring, do not connect inductive
loads to the supply voltage or the digital inputs/outputs without free running diodes.
For more information on digital inputs or outputs, refer to chapter "Technical data and
dimension drawings"(→275).
6.2.7 X32/X33: CAN2/CAN1 system bus interface
Function
Do not connect more than 16 devices to the CAN1 or CAN2 system bus. The sys-
tem bus supports the address range 0 to 63.
Connection type
Spring terminal plug connector
CAN 1 wiring diagram
DGND
MOVIDRIVE
MDX60B/61B
X12
SC11
2
1
3
SC12
DHE41B
X31X32X33
1
2
3
1
2
3
1
2
3
2
3
1
SC11
DGND
ON OFF
S12
X12:
2
1
SC12
3
ON OFF
S12
X45
X46
1
2 3 4 5 6H L ⊥
FSC11B
MOVITRAC
®
B
S1
OFF
ON
7
S2
X44
®
MOVIDRIVE MDX61B
®
9007201357202827
Assignment: CAN2 system bus interface (electrically isolated)
No. Name Function
X32 1 REF_CAN 2 Reference potential for system bus CAN 2
2 CAN2H System bus CAN2 high
3 CAN2L System bus CAN 2low
22900055/EN – 08/2016