6
Electrical installation
Terminal assignment and DIP switches
Manual – DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
31
Setting the station address
To set the PROFIBUS station address, use DIP switches 2
0
–2
6
on the DHF21B/41B
option card. The DHF21B/41B option card supports address range 0–125.
2103383051
The default setting for the station address is 4:
2
0
→Significance: 1×0 = 0
2
1
→Significance: 2×0 = 0
2
2
→Significance: 4×1 = 4
2
3
→Significance: 8×0 = 0
2
4
→Significance: 16×0 = 0
2
5
→Significance: 32×0 = 0
2
6
→Significance: 64×0 = 0
Any change made to the PROFIBUS station address during ongoing operation does
not take effect immediately. You have to switch the compact controller or the inverter
in which the DHF21B/41B option card is installed on and off again for the changes to
take effect (power +24V off/on).
6.2.5 X30D: DeviceNet
TM
connection
Function
Connection to the DeviceNet
TM
fieldbus system
Connection type
The DHF21B/41B option card is opto-decoupled on the driver side in accordance
with the DeviceNet
TM
specification (VolumeI, Chapter9). This means the CAN bus
driver must be powered with 24V voltage via the bus cable. The cable to be used is
also described in the DeviceNet
TM
specification (VolumeI, AppendixB). The connec-
tion must be made according to the color code specified in the "Assignment" table.
Wiring diagram
The following figure shows the 5‑pin Phoenix terminal that is connected to X30D of
the DHF21B/41B option card.
The assignment of connecting terminals is described in the DeviceNet
TM
specification
(VolumeI, AppendixA).
22900055/EN – 08/2016