66 DUSTHUNTER T · Operating Instructions · 8012428 V 2.0 · © SICK MAIHAK GmbH Germany
Start-up and Parameter Settings
4.4.2 Factory settings
*: Only if optional analog module is available (standard at DUSTHUNTER T100 and T200) )
The steps required to modify these settings are described in the following Sections.
Prerequisites: The device data are located in the "Project tree“ window, the Level 1
password and "Maintenance" mode are set.
Parameter Value
Check cycle Every 8 h; output of check values (90 s for every
value) on standard analog output
Analog output (AO)
[mA]
Live zero (LZ) 4
Upper measuring range value
(MBE)
20
Current during maintenance 0.5
Current by malfunction 21 (optional 1)
Response time 1 s for all measured variables
Measured variable Output on AO Value at LZ Value at MBE
Transmission [%] 100 0
Opacity [%] 1 0 100
Extinction 3 * 0 2
Dust concentration [mg/m³] 2 * 0 200
Regression coefficients (only for dust concentration) 0.00 / 1.00 / 0.00