Unsafe inputs and outputs also make it possible to evaluate certain situations (e.g. con‐
t
amination) on the monitored system or to trigger functions (e.g. illumination of lamps
and activation of door locking devices).
Special features
up to 32 Flexi Loop nodes per safe sensor cascade
up to 100 m between Flexi Loop nodes and up to 3,200 m total length of the safe
sensor cascade
up to 10 m cable length between the Flexi Loop nodes and the devices connected
optional status indication via DIAG Flexi Loop accessory
optional power supply by means of PWRI power supply accessory
enclosure rating IP 65 and IP 67 to EN 60529
Connection to safety controllers:
Flexi Soft safety controller
Flexi Classic safety controller
up to 8 safe sensor cascades on one Flexi Soft safety controller
up to 48 safe sensor cascades on one Flexi Classic safety controller
3.1.1 System requirements
Flexi Soft safety controller
The saf
e sensor cascade is connected directly to a Flexi Soft safety controller extension
module. The following prerequisites apply:
one main module
°
FX3-CPUx with firmware V3.xx or higher
one or more expansion modules
°
FX3-XTIO with firmware V3.xx or higher
°
FX3-XTDI with firmware V3.xx or higher
°
FX3-XTDS with firmware V3.xx or higher
Flexi Classic safety controller
The saf
e sensor cascade is connected to the main module or a Flexi Classic safety con‐
troller extension module with a Flexi Loop MSTR accessory. The following prerequisites
apply:
one main module
°
UE410-MU version 13.45 or higher
one Flexi Loop MSTR1 or MSTR2 accessory
one or more extension modules (optional)
°
UE410-XU version 13.45 or higher
°
UE410-8DI version 13.45 or higher
3.1.2 Safety by means of Flexi Loop
P
erformance level up to PL e
°
dependent on the performance level of the overall application
°
independent of the number of Flexi Loop nodes and thus the number of sen‐
sors / switches
°
independent of whether the sensors / switches are directly connected to the
safety controller or to the safe sensor cascade
one cut-off path; the status of this path is represented in the Flexi Soft logic by
means of a single safe bit. This feature permits quick, safe shutdown.
no error masking
3 PR
ODUCT DESCRIPTION
12
O P E R A T I N G I N S T R U C T I O N S | Flexi Loop 8015836/YT10/2016-05-24 | SICK
Subject to change without notice

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK Flexi Loop and is the answer not in the manual?

SICK Flexi Loop Specifications

General IconGeneral
BrandSICK
ModelFlexi Loop
CategoryAccessories
LanguageEnglish

Related product manuals