8 FAULT DIAGNOSIS
182
8017768/12AX/2019-05-31|SICK
OPERATING INSTRUCTIONS | TIC
Subject to change without notice
Incorrect number of axles
Possible cause
Remedy
The LMS Axle was not mounted in
accordance with the specifications
(mounted too high, angle of incidence too
steep, etc.)
Make sure that the device is mounted in
accordance with the specifications (see chapter
3.6.5 Requirements for mounting the axle
counting components).
The LMS Axle’s visual range has been
blocked by outside ambient conditions,
e.g., snow, temporary lane barriers.
Check that the visual range of the 2D LiDAR
sensor is clear.
Clear away anything that is blocking the
2D LiDAR sensor’s measuring range.