54 Hardware Description CNC 0610510/12 CNC 61.00
8.3 Error Indications FC0 to FC3 ( Red Flashing)
X LED is continuously red: permanent error, e.g. emergency stop
X LED is flashing red: error occurred and must be reset via the software
E LED is off
F LED flashes
D LED is on:
LEDs Code* error Reaction Possible reason
EE
EE
0 no error no
EE
ED
129
active monitor-
ing of travel area
reference position = actual
position
reference speed = 0
this error occurs if the limit switches of the software
are activated in the parameter file.
X The limit switches of the software in the para-
meter file are incorrectly parameterized.
EE
DE
130
14 V not provid-
ed
reference speed = 0 and
controller OFF
1
X possibly the option module has not been moun-
ted correctly.
EE
DD
131
-14 V not provid-
ed
reference speed = 0 and
controller OFF
1
X possibly the option module has not been moun-
ted correctly.
ED
EE
132 short circuit
reference speed = 0 and
controller OFF
1
double peak current flows via the measuring shunt
into the output stage.
X error when wiring the motor cables
X a motor cable is parted or the motor cables are
pinched (especially a ground cable)
X if the motor cables are pulled off the backpanel,
the output stage of the CNC61 is defective
ED
ED
133 reserved no
ED
DE
134
overvoltage/
undervoltage
ref. speed = 0 and controller
off
1,2
overvoltage:
230 V
AC
method = cutoff threshold 385 V
400 VAC method = cutoff threshold 810 V
X the external supply of 24 V is faulty
X the main voltage supply of the power module is
faulty (the voltage is too high)
X the ballast resistor is not connected correctly
X the braking power of the power module is ex-
ceeded
undervoltage: voltage < 42 V
24 V are not provided
24 V internal:
- overvoltage protection has responded
24 V external:
- 24 V are not provided
X the external supply of 24 V is faulty
X protective circuit of 24 V in the CNC61 has re-
sponded
X the main voltage supply of the power module is
faulty (the voltage is too low)
ED
DD
135
error of first
measuring sys-
tem
reference speed = 0 and
controller OFF
1
X a cable of the measuring system is parted or the
cables are pinched (especially a ground cable)
X the connector of the first measuring system (X1)
is not connected or not correctly connected
X the wiring of connector X1 at the backpanel or
of the resolver connector at the motor is faulty
DE
EE
136
motor-
Temperature
reference speed = 0 and
controller OFF
1
the motor is too hot
X due to overload, the motor became to hot
X PTC (NTC) is not correctly connected
X the connection from the CNC61 to the PTC is in-
terrupted