Commissioning
S7-300 Programmable Controller Hardware and Installation
8-14 A5E00105492-01
Table 8-3 Possible causes of a CPU request to reset memory
Causes of a CPU request to reset
memory
Remarks
The Memory Card or MMC has been
replaced.
not with CPU 312 IFM /
314 IFM (314-5AE0x)
RAM error in CPU –
Main memory too small, that is not all
user program blocks on a Memory
Card or MMC could be loaded.
Attempts to load faulty blocks; e.g. if
the wrong instruction was
programmed.
CPU with inserted 5-V FEPROM Memory Card
(not CPU 31x)
With these causes the CPU requests one
memory reset. After that, the CPU ignores the
contents of the memory card, enters the error
reasons in the diagnostics buffer and goes to
STOP. You can erase or reprogram 5-V
FEPROM Memory Card in the CPU.
CPU 31xC with inserted MMC: Continuous
request to reset memory.
Additional information on MMC behavior after
memory reset is found in the Reference Manual
CPU Data , Chapter memory Conception.
How to reset memory
There are two ways of resetting CPU memory:
Memory reset with the mode selector
switch
Memory reset with PG
... is described in this Chapter. ... only possible if the CPU is in STOP mode
(seeSTEP 7 Online Help).

Table of Contents

Other manuals for Siemens 6ES7 305-1BA80-0AA0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 6ES7 305-1BA80-0AA0 and is the answer not in the manual?

Siemens 6ES7 305-1BA80-0AA0 Specifications

General IconGeneral
BrandSiemens
Model6ES7 305-1BA80-0AA0
CategoryController
LanguageEnglish

Related product manuals