3-11
Operation
the list of security conditions;
[custom message] is a custom
message entered using the CSG-M
Custom Software Generator (See the
CSG-M Programming Manual, P/N 315-
090381); [device type] is the type of
device which reported the security
condition.
Viewing the List of Security Conditions
To see the security condition list when
there is more than one security condi-
tion, press NEXT on the MKB (the
System displays the most recent
security condition first).
How to Individually Acknowledge a
Security Condition (UL 1076)
Press SEC ACK. The System ac-
knowledges the security condition
displayed and then displays the next
unacknowledged security condition.
If your System has a printer, it prints
an acknowledgment message
similar to the following:
ACK Security 1-5 12:01:28 Dec 31,20xx
#2 [custom message], [device type]
Note that the acknowledgment
message includes the term ACK to
indicate this security condition was
acknowledged.
Continue acknowledging security
conditions as explained above until
the System displays the following
message:
ALL SECURITY CONDITIONS
ACKNOWLEDGED
The SECURITY LED glows steadily
to indicate that all security conditions
are acknowledged, and the internal
audible goes silent.
If your System includes a printer,
it prints the following message:
ACK Security 12:05:44 DEC 31, 20xx
All Security Conditions Are Now Acknowledged.
Reset Procedures
Hard Reset
Other terms for Hard Reset are
Power-up, Initialization, and Cold
Reset.
Applying power to the System per-
forms a Hard Reset. Doing so initial-
izes the whole system.
What Is Lost:
Alarms, supervisories, troubles,
security conditions (provided they
have returned to the normal state).
Any user entries such as time and
date (MMB-1 only).
Arm/disarm.
Manual sensitivity adjustment.
Time-based control until time is
reset (MMB-1 only).
What Is
Not Lost:
CSG-M program.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus PYROTRONICS MXL and is the answer not in the manual?

Siemens Cerberus PYROTRONICS MXL Specifications

General IconGeneral
BrandSiemens
ModelCerberus PYROTRONICS MXL
CategoryControl Panel
LanguageEnglish

Related product manuals