1-10
Description
CSM-4 Signal Module
The CSM-4 Signal module controls two
supervised notification appliance
circuits. Each circuit is capable of
either Style Z (Class A) or Style Y
(Class B) operation. Each circuit can be
individually configured for notification
appliances, municipal tie, leased line,
or releasing service per NFPA 12A, 13
and 2001.
CRM-4 Relay Module
The CRM-4 Relay module is an output
control module that contains four relay
outputs. Form C contacts are rated at
2A, 30 VDC/120 VAC resistive.
CZM-4 Conventional Zone Module
The CZM-4 Conventional Zone module
provides four initiating device circuits
capable of Style D (Class A) or Style B
(Class B) operation. Each zone sup-
ports up to thirty two-wire detectors,
one linear beam detector or an unlim-
ited number of shorting devices. Each
zone has its own address. You can use
the CSG-M to write a custom message
for each zone (See the CSG-M Pro-
gramming Manual, P/N 315-090381).
CRM-4 Relay Module
CZM-4 Conventional Zone Module
CSM-4 Signal Module
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus PYROTRONICS MXL and is the answer not in the manual?

Siemens Cerberus PYROTRONICS MXL Specifications

General IconGeneral
BrandSiemens
ModelCerberus PYROTRONICS MXL
CategoryControl Panel
LanguageEnglish

Related product manuals