1-33
Description
FP-11 Intelligent/Analog
Photoelectric Detector
1
The FP-11 is an intelligent/analog
photoelectric detector that can be used
as an area or duct detector [FP-11(d)].
It uses either a DB-11 low profile
mounting base or DB-3S mounting
base with the DB-ADPT adapter, a
DB-X11RS mounting base with relay
or DB-X3RS mounting base with relay
with the DB-ADPT adapter, an ADBI-60
audible base with the DB-ADPT adapter,
or an AD-11P or AD-11XPR air duct
housing. The FP-11 requires MXL Rev
10.0 or higher firmware.
FPT-11 Intelligent Thermal Detector
The FPT-11 is an intelligent/analog rate-
compensated/fixed-temperature type
thermal and photoelectric detector. It
can only be used as an area detector. It
uses either a DB-11 low profile mount-
ing base or DB-3S mounting base with
the DB-ADPT adapter, a DB-X11RS
mounting base with relay or DB-X3RS
mounting base with relay with the
DB-ADPT adapter, or an ADBI-60
audible base with the DB-ADPT adapter.
The FPT-11 requires MXL Rev. 10.0 or
higher firmware.
ID-60P Intelligent/Analog
Photoelectric Detector
1
The ID-60P is an intelligent/analog
photoelectric detector that can be used
as an area or duct detector [ID-6OP(d)].
It uses either a DB-3S low profile
mounting base, a DB-X3RS mounting
base with relay, an AD-3P duct hous-
ing, or an ADBI-60 audible base.
ID-60PT Intelligent/Analog Photo-
electric Detector with Heat Sensor
1
The ID-60PT is an intelligent/analog
rate-compensated/fixed-temperature
type thermal and photoelectric detec-
tor. It can only be used as an area
detector. It uses either a DB-3S low
profile mounting base, a DB-X3RS
mounting base with relay, or an
ADBI-60 audible base.
ID-60I Intelligent/Analog lonization
Detector
1
The ID-60I is an intelligent/analog
ionization detector for use in open
areas at altitudes of 0 to 4000 feet. It
uses either a DB-3S low profile mount-
ing base, a DB-X3RS mounting base
with relay, or an ADBI-60 audible base.
ID-60IH Intelligent/Analog lonization
High Altitude Detector
1
The ID-60IH is an intelligent/analog
ionization detector for use in open areas
at altitudes of 3000 to 8000 feet. It uses
either a DB-3S low profile mounting
base, a DB-X3RS mounting base with
relay, or an ADBI-60 audible base.
ID-60IA Intelligent/Analog lonization
High Air-Velocity Detector
1
The ID-60IA is an intelligent/analog
ionization high air-velocity detector for
use in open areas, computer facilities,
and air ducts at altitudes of 0 to 4000
feet, with air velocities of 0 to 1200
feet per minute. It uses either a DB-3S
low profile mounting base, a DB-X3RS
mounting base with relay, or an
ADBI-60 audible base.
Analog
Addressable
Devices
NOTES
1. Refer to Appendix F,
Envirolink
2. Refer to Appendix I,
Application Specific
Detection (ASD)
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus PYROTRONICS MXL and is the answer not in the manual?

Siemens Cerberus PYROTRONICS MXL Specifications

General IconGeneral
BrandSiemens
ModelCerberus PYROTRONICS MXL
CategoryControl Panel
LanguageEnglish

Related product manuals