4 - 54
MOM-4 Connections and Ratings
Determine which optional plug-in
modules are used in your CSG-M
configuration. Depending on the
optional modules used, determine the
outstanding power by using the table
in Appendix D - MXL Power Supply
Load Calculations on page D-2. (See
the EXAMPLE). This power can be
used for notification appliances or for
the optional power connector on TB5.
NOTE: When a CSM-4 is used, you
may add notification appliances to it
if the maximum load current to the
MOM-4 does not exceed 2 amps
(MMB-1); or with a PSR-1/MMB-2,
6 amps (MPS-6/6W) or 12 amps
(MPS-12/12W). Include the total alarm
current on each CSM-4 notification
appliance circuit when performing the
calculations.
EXAMPLE:
With: one CZM-4 and
one CRM-4 and
one CSM-4
Total load current =
0.720 + 0.075 + 0.034 = 0.83A
With MPS-6/6W:
Remaining Available Current =
2.0 - 0.83 = 1.17A (MMB-1)
6.0 - 0.83 = 5.17A (PSR-1/MMB-2)
with no CZM-1B6 or PS-5A/-5N7 load
With MPS-12/12W:
Remaining Available Current =
2.0 - 0.83 = 1.17 (MMB-1)
12.0 - 0.83 = 11.17 (PSR-1/MMB-2)
with no CZM-1B6 or PS-5A/-5N7 load
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus PYROTRONICS MXL and is the answer not in the manual?

Siemens Cerberus PYROTRONICS MXL Specifications

General IconGeneral
BrandSiemens
ModelCerberus PYROTRONICS MXL
CategoryControl Panel
LanguageEnglish

Related product manuals