4 - 54
MOM-4 Connections and Ratings
Determine which optional plug-in
modules are used in your CSG-M
configuration. Depending on the
optional modules used, determine the
outstanding power by using the table
in Appendix D - MXL Power Supply
Load Calculations on page D-2. (See
the EXAMPLE). This power can be
used for notification appliances or for
the optional power connector on TB5.
NOTE: When a CSM-4 is used, you
may add notification appliances to it
if the maximum load current to the
MOM-4 does not exceed 2 amps
(MMB-1); or with a PSR-1/MMB-2,
6 amps (MPS-6/6W) or 12 amps
(MPS-12/12W). Include the total alarm
current on each CSM-4 notification
appliance circuit when performing the
calculations.
EXAMPLE:
With: one CZM-4 and
one CRM-4 and
one CSM-4
Total load current =
0.720 + 0.075 + 0.034 = 0.83A
With MPS-6/6W:
Remaining Available Current =
2.0 - 0.83 = 1.17A (MMB-1)
6.0 - 0.83 = 5.17A (PSR-1/MMB-2)
with no CZM-1B6 or PS-5A/-5N7 load
With MPS-12/12W:
Remaining Available Current =
2.0 - 0.83 = 1.17 (MMB-1)
12.0 - 0.83 = 11.17 (PSR-1/MMB-2)
with no CZM-1B6 or PS-5A/-5N7 load