E - 2
Appendix E
With Device Confirmation, the BðC
verification time known as System
Justified Alarm time is also adjustable.
It is the same time used by both
ionization and photo detectors. If a
device is individually selected for alarm
verification, the alarm verification
feature takes priority over the device
confirmation option. For adjustment
ranges, refer to the CSG-M Program-
ming Manual, P/N 315-090381.
There is an Override menu selection in
the Test menu of revision level 3.00 or
higher of MXL. Select Alr_Verify to
disable all alarm verification or select
Alr_Confirm to disable all alarm confir-
mation for a period of up to 4 hours or
until manually re-enabled.