K-6
Appendix K
Trouble Message The Probable Cause Is:
Incorrect Library Version There is an incompatibility between the
library CSG-M selection and the DMC-1
library chip. There is an incorrect factory
recorded selection.
Incorrect Node Address Address on NIM-1R is incorrect.
Incorrect Submodule ID Incorrect OCC-1 or ACM-1 submodule
installed or programmed incorrectly.
Input Dev Response Too Low Input wiring to TRI, ICP-B6, and
CZM-1B6 modules has an open circuit
or no EOL. Loss of power to ICP-B6 or
CZM-1B6 modules. Smoke detector
chamber defective.
Input Device Not Responding A device assigned in CSG-M is not
reporting at its address.
Input Device Requires Service An ion or photo detector has exceeded
the 80% dust threshold.
Input Disarmed An initiating device was disarmed
through the Control menu.
Keyswitch Activated (CANADA) This is a trouble type for activation of
Canadian manual station keyswitch if no
alarm is present.
Lamp Supervision Trouble MID-1 input trouble when used for lamp
supervision.
Local Audio Riser Open circuit detected on the RCM-1 D
Riser.
Log FULL, Events Will Be Lost History Log is full. Use extract history
in CSG-M to reset the MXL history log
Loss of 24V Input Power A CZM-4 has lost its 24 VDC input.
Low Battery Voltage MMB or PSR-1 low battery condition.
Low IEC Voltage, Service Req Defective device.