K-12
Appendix K
Trouble Message The Probable Cause Is:
Unspecified Mod Responding A module has reported at an address
not assigned in CSG-M.
Unspecified Node Responding  NIM-1R address on another node is
incorrect.
 The network CSG-M is incorrect.
Unspecified Submodule Responding A submodule has been reported at an
address not assigned in CSG-M.
WALKTEST Activated The MXL has been placed in the walk
test mode.
Warm Reset The hardware reset input to the MXL
was used.
Watch Dog Circuit Triggered The watch dog circuit on the
MMB-1/-2 triggered.
Zone Loop Open Broken wire on CZM-4 circuit.
Zone Loop Shorted Shorted wire on CZM-4 circuit.
Zone Power Loss The CZM-4 zone at this address has lost
its 24 volt input.