7.2.1  General 
 
The details page for cascade controllers can be reached multiple ways, including: 
–  Main Index > Unit > Temp control > Cascade controller 
–  Main Index > Unit > Humidity control > Cascade controller 
–  Main Index > Unit > Loop controllers > Casc controller tmp 
–  Main Index > Unit > Loop controllers > Casc controller hum 
 
 
Parameter  Range  Function 
Control output clg     Present controller output for cooling setpoint or 
dehumidification setpoint. 
Control output htg    Present controller output for heating setpoint or 
humidification setpoint. 
Present Value     Present actual value (input value) for the control-
ler. 
Room stpt clg/dehum    Cooling or dehumidification setpoint from the 
program. 
Room stpt htg/hum 
 
  Heating or humidification setpoint from the pro-
gram. 
High limit   -64.0 …99.0 [°C] / [% rH]  Maximum supply air temperature or humidity. 
Low limit   -64.0…99.0 [°C] / [% rH]  Minimum supply air temperature or humidity. 
Load compensation  -64.0…99.0 [°C] / [% rH]  Set compensation for a room load. Calculates 
the present controller outputs as follows: 
−  Control output clg = Internally calculated Con-
trol Output clg + Load compensation 
−  Control output htg = Internally calculated 
Control Output htg + Load compensation 
Setpoint selection  −  Htg+Dz 
−  Htg/Clg 
−  +/-Half Dz 
−  Clg-Dz 
Displays setpoint variants in the program (Con-
figuration 2 >Tmp stpt selection or Hum stpt se-
lection). 
Setpoint dead zone 
 
  From the entry of calculated dead zones. (Dis-
plays dead zones: Configuration 2 >Tmp stpt 
selection or Hum stpt selection). 
Enable.   
−  Passive  
−  Active 
Enable controller: 
−  Controller disabled. 
−  Controller enabled. 
Fault   
 
−  Passive  
−  Active 
Controller fault status (e.g. faulty sensor signal): 
−  No error. 
−  Error pending. Does not trigger an event, 
since the cause of a control fault must be re-
corded separately (e.g. room sensor fault). 
Access 
Parameter 