113 / 244 
Siemens  Standard application AHU  CE1P3977en_02 
Building Technologies  Detail pages: Controller  01.02.2010 
Parameter  Range  Function 
Status   
−  GESP 
−  UL 
−  LL 
−  REG 
−  UDEF 
Controller status: 
−  Controller disabled. 
−  Control output = High limit. 
−  Control output = Low limit. 
−  Control mode. 
−  Undefined. 
Special settings    Go to Special settings page (at access levels 4 
and 2 only). 
 
 
7.2.2  Special settings 
 
Parameter  Range  Function 
Gain  0...1000  −  Amplification factor (KP).  
Int action time  0….18000
 
[s]  Integral action time (Tn).  
Min/max limit  -64.0…99.0 [°C] / [% rH] 
 
Adjusts high und Low limits to end position. En-
sures the difference between heating and cool-
ing output in the end position as well as needed. 
 
Min/max limit positiv: 
−  Niedrigster Control output clg = Low limit + Min/max limit 
−  Niedrigster Control output htg = Low limit 
 
Min/max limit negativ: 
−  Niedrigster Control output clg = Low limit 
−  Niedrigster Control output htg = Low limit - Min/max limit 
 
Min/max limit positiv: 
−  Niedrigster Control output clg = High limit 
−  Niedrigster Control output htg = High limit - Min/max limit 
 
Min/max limit negativ: 
−  Niedrigster Control output clg = High limit + Min/max limit 
−  Niedrigster Control output htg = High limit 
 
High limit = 28 
Low limit = 16 
Min/max limit = -2 
Cooling: 
−  Lowest control output clg = Low limit => 16. 
−  Lowest control output htg = Low limit - Min/max limit => 16 – 2 = 14. 
 
Heating: 
−  Lowest control output htg = High limit + min/max limit => 28 – 2 = 30. 
−  Lowest control output htg = High limit => 28. 
 
Function during cooling 
Function during heating 
Example 
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 113